Insulation Code | Insulation Type | Appearance | Insulation Temperature Range* | Abrasion Resistance | Flexibility | Water Submersion | |
---|---|---|---|---|---|---|---|
Overall | Conductors | ||||||
PP |
Polyvinyl Chloride (PVC) |
Polyvinyl Chloride (PVC) |
-40 to 105°C |
Good |
Excellent |
Good | |
FF |
FEP |
FEP |
-200 to 200°C |
Excellent |
Good |
Excellent | |
TT |
PFA |
PFA |
-267 to 260°C |
Excellent |
Good |
Excellent |
Insulation Code | Resistance To: | Comments | ||||
---|---|---|---|---|---|---|
Solvent | Acid | Base | Flame | Humidity | ||
PP |
Fair |
Good |
Good |
Good |
Good |
Color Coded PVC Extruded Over Each Bare Wire. PVC Applied Over Insulated Primaries. Affected by Ketones, Esters |
FF |
Excellent |
Excellent |
Excellent |
Excellent |
Excellent |
Color Coded FEP Extruded Over Each Bare Wire. FEP Jacket Extruded Over Insulated Primaries, Superior Abrasion and Moisture Resistance. Same Basic Characteristics as PFA but Lower Temperature Rating |
TT |
Excellent |
Excellent |
Excellent |
Excellent |
Excellent |
Color Coded FEP Extruded Over Each Bare Wire. PFA Jacket Extruded Over Insulated Primaries, Superior Abrasion and Moisture Resistance. Same Basic Characteristics as FEP but Higher Temperature Rating |